| A security issue affecting multiple Cisco devices also directly impacts Stratix® 5410, 5700, and 8000 devices. This can lead to remote code execution by uploading and running malicious configurations without authentication. |
| Multiple denial-of-service vulnerabilities exist in the affected product. These issues can be triggered through various crafted inputs, including malformed Class 3 messages, memory leak conditions, and other resource exhaustion scenarios. Exploitation may cause the device to become unresponsive and, in some cases, result in a major nonrecoverable fault. Recovery may require a restart. |
| A security issue exists due to improper handling of malformed CIP Forward Close packets during fuzzing. The controller enters a solid red Fault LED state and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF015. To recover, clear the fault. |
| A security issue exists within the 5032 16pt Digital Configurable module’s web server. The web server’s session number increments at an interval that correlates to the last two consecutive sign in session interval, making it predictable. |
| A security issue was discovered within the legacy Ansible playbook component of Verve Asset Manager, caused by plaintext secrets incorrectly stored when a playbook is running. This component has been retired and has been optional since the 1.36 release in 2024. |
| A security issue exists due to improper handling of malformed CIP packets during fuzzing. The controller enters a hard fault with solid red Fault LED and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF019. To recover, clear the fault. |
| A code execution security issue exists in the affected product. An attacker with physical access could abuse the maintenance menu of the controller with a crafted payload. The security issue can result in arbitrary code execution. |
| A denial-of-service security issue exists in the affected product and version. The security issue is caused through CIP communication using crafted payloads. The security issue could result in no CIP communication with 1715 EtherNet/IP Adapter.A restart is required to recover. |
| A security issue was discovered within Verve Asset Manager allowing unauthorized read-only users to read, update, and delete users via the API. |
| CVE-2024-6078 IMPACT
An improper authentication vulnerability exists in the affected product, which could allow a malicious user to generate cookies for any user ID without the use of a username or password. If exploited, a malicious user could take over the account of a legitimate user. The malicious user would be able to view and modify data stored in the cloud. |
| A security issue exists within 432ES-IG3 Series A, which affects GuardLink® EtherNet/IP Interface, resulting in denial-of-service. A manual power cycle is required to recover the device. |
| A vulnerability exists in the Rockwell Automation Emulate3D™, which could be leveraged to execute a DLL Hijacking attack. The application loads shared libraries, which are readable and writable by any user. If exploited, a malicious user could leverage a malicious dll and perform a remote code execution attack. |
| A security issue was discovered within the legacy ADI server component of Verve Asset Manager, caused by plaintext secrets stored in environment variables on the ADI server. This component has been retired and has been optional since the 1.36 release in 2024. |
| An improper authorization vulnerability exists in the Rockwell Automation affected products that could allow an unauthorized user to sign in. While removal of all role mappings is unlikely, it could occur in the case of unexpected or accidental removal by the administrator. If exploited, an unauthorized user could access data they previously but should no longer have access to. |
| A security issue was discovered within FactoryTalk® ViewPoint, allowing unauthenticated attackers to achieve XXE. Certain SOAP requests can be abused to perform XXE, resulting in a temporary denial-of-service. |
| A security issue exists within the 5032 16pt Digital Configurable module’s web server. Intercepted session credentials can be used within a 3-minute timeout window, allowing unauthorized users to perform privileged actions. |
| A Remote
Code Execution vulnerability exists in the affected product. The vulnerability requires
a high level of permissions and exists due to improper input validation resulting
in the possibility of a malicious Updated Agent being deployed. |
| An
authentication bypass vulnerability exists in the affected product. The
vulnerability exists due to shared secrets across accounts and could allow a threat
actor to impersonate a user if the threat actor is able to enumerate additional
information required during authentication. |
| A security issue was discovered in DataMosaix Private Cloud, allowing users with low privilege to perform sensitive database operations through exposed API endpoints. |
| A security issue exists due to improper handling of CIP Class 32’s request when a module is inhibited on the 5094-IY8 device. It causes the module to enter a fault state with the Module LED flashing red. Upon un-inhibiting, the module returns a connection fault (Code 16#0010), and the module cannot recover without a power cycle. |